I/O enclosure LED indicators (Models 951, 95E)

This section contains FRUs that have LED indicators. Each listed assembly is shown with a description of its LEDs. Do not use LEDs as a starting point for diagnosing a problem.

I/O enclosure FRUs with LEDs

Table 1. I/O enclosure locations (front)
Part Reference
I/O enclosure fan Figure 1
I/O enclosure power supply Figure 1
Table 2. I/O enclosure locations (rear)
Part Reference
PCIe/SPCN card Figure 2
I/O enclosure backplane assembly Figure 2
I/O enclosure device adapter card Figure 2
I/O enclosure Fibre Channel host card Figure 2

I/O enclosure front

Figure 1. LEDs on the I/O enclosure (front)
LEDs on the I/O enclosure (front)
Table 3. Interpreting the LEDs on the I/O enclosure (front)
Index LED Function Location Color LED Off LED On LED Flash
1 Input power for I/O enclosure power supply E1 green no input input good n/a
2 Output power for I/O enclosure power supply E1 green standby off output on standby
3 Identify for I/O enclosure power supply E1 amber normal n/a fast = identify, slow = com fail
4 Input power for I/O enclosure power supply E2 green no input input good n/a
5 Output power for I/O enclosure power supply E2 green standby off output on standby
6 Identify for I/O enclosure power supply E2 amber normal n/a fast = identify, slow = com fail
7 Identify for I/O enclosure fan A1 amber normal n/a identify
8 Identify for I/O enclosure fan A2 amber normal n/a identify
9 Identify for I/O enclosure P1 blue normal identify n/a
10 Power for I/O enclosure P1 green power off power on standby

I/O enclosure rear

Figure 2. LEDs on the I/O enclosure (rear)
LEDs on the I/O enclosure (rear)
Table 4. Interpreting the LEDs on the I/O enclosure (rear)
Index LED Function Location Color LED Off LED On LED Flash
1 Power for I/O enclosure PCIe/SPCN card P1-C7 green power off power on power standby
2 Identify for I/O enclosure PCIe/SPCN card P1-C7 amber normal fault identify
3 Power for I/O enclosure P1 green power off power on n/a
4 Power for I/O enclosure PCI slot P1-Cx green power off power on standby (card regulators off)
5 Identify for I/O enclosure PCI slot P1-Cx amber normal n/a identify
6 Activity for I/O enclosure device adapter card port P1-Cx-Ty x=3, 6 green not ready
Note 1
ready
Note 2
n/a
7 Identify for I/O enclosure device adapter card port P1-Cx-Ty x=3, 6 amber normal n/a identify
8, 9 Fibre channel host card port LEDs (see Table 5 and Table 6) P1-Cx-Ty x=1,4        
Notes:
  1. LED off indicates port is not ready.
  2. LED on solid indicates port is ready (link is operational).

Fibre channel host card port LEDs

Table 5 and Table 6 provide detailed information on fibre channel host card port LEDs.
Important: Do not replace host adapter cards based on visual symptoms displayed in the LEDs. Replace them only when they are:
  • Listed in a serviceable event FRU list, OR
  • Isolated in an isolation procedure MAP
Note: In the following tables, LED terms are:
  • Slow blinks are 1 per second
  • Fast blinks are 4 per second
  • Flashing is very fast blinking; the, LED may look dimly lit
Table 5. Fibre channel host card port LEDs (normal conditions)
Adapter Yellow LED Green LED State
8-Gb/s adapters Off Slow blink Normal - link is down or not started
2 blinks On 2-Gb/s link rate - normal, link is up
3 blinks On 4-Gb/s link rate - normal, link is up
4 blinks On 8-Gb/s link rate - normal, link is up
Table 6. Fibre channel host card port LEDs (Power up, failure, download, or test conditions)
Adapter Yellow LED Green LED State
8-Gb/s adapters Off Off Wake-up failure (dead board)
On Failure when functioning
On Off POST failure (dead board)
On Failure when functioning
Slow blink Off Wake-up failure monitor
Slow blink Offline for download
Fast blink Off POST failure
Slow blink Restricted offline mode (waiting for restart)
Flashing Off POST process in progress
Slow blink Restricted offline mode (test active)