MAP2140 Unable to power off from a System z host system
When the System z® remote power feature is installed, the first rack contains a ZLR type of local remote switch card. The DIP switch that is on each RPC card will have switch 3 set to the on (right) position. A failure that disables the remote power control can be internal or external to the storage facility.
Before you begin
- The feature is properly installed
- System z feature switch is set to ON (right) on both RPC logic cards
- All cable connections are correct
- The System z local remote switch card switch is set to Remote
- The management console is available and the power control mode at the management console is set to System z remote.
About this task
MAP2140 Section-1
Before you begin
About this task
Note: You can temporarily bypass the failure to power off as described in step 4.