MAP2341 Codes on the DC-UPS DSU status display

The DC-UPS status display on the front of the DC-UPS indicates status and error conditions. Error conditions that are displayed create serviceable events. Use the serviceable events to guide the repair.

MAP2341 Section-1

Procedure

  1. The DC-UPS is displaying an error code, which is defined in Table 1. A serviceable event is created unless the DC-UPS is in a rack that is not yet fully installed.
  2. During DC-UPS power on, the DC-UPS status display shows the DC-UPS firmware level and DC-UPS identification. DC-UPS firmware level is also available through the management console utilities to display the installed code levels.
    The following sequence of characters is displayed:
    XX > yy > zz > Du 
  3. After DC-UPS power on, the status display is normally blank.
    Table 2. DC-UPS input conditions
    Status code Description
    I0 Local AC loss
    I1 AC input phase missing
    I2 Input CB1 tripped
    I4 Input CB1 switched off
    I5 DC-UPS Power On Self Test failed
    Table 3. DC-UPS output conditions
    Status code Description
    O0 TBD
    O1 TBD
    Table 4. DC-UPS internal and communication conditions
    Status code Description
    CM Main CPU and phase CPU firmware mismatch
    X0 Converter 7.5V (RPC) fault
    X1 TBD
    X2 Converter 12V (FAN) fault
    X3 Converter 24V (EPO) fault
    X6 Phase 0 communication failure
    X8 Phase 1 communication failure
    X9 Phase 2 communication failure
    XA DC-UPS1 to DC-UPS2 communication failure
    XC TBD
    XD TBD
    XE DC-UPS to RPC0 (RPC1 card) communication failure
    XF DC-UPS to RPC1 (RPC2 card) communication failure
    XY No valid firmware image. Display controlled by boot code
    Table 5. DC-UPS fan conditions
    Status code Description
    F0 Fan0 fault
    F1 Fan1 fault
    Table 6. DC-UPS phase 1 issues
    Status code Description
    R0 Main output failure
    R1 DDM output failure
    R2 Partner input loss
    R3 Over temperature
    R4 TBD
    Table 7. DC-UPS phase 2 issues
    Status code Description
    S0 Main output failure
    S1 DDM output failure
    S2 Partner input loss
    S3 Over temperature
    S4 TBD
    Table 8. DC-UPS phase 3 issues
    Status code Description
    T0 Main output failure
    T1 DDM output failure
    T2 Partner input loss
    T3 Over temperature
    T4 TBD
    Table 9. Battery service module conditions
    Status code Description
    U0 BSM0 fault
    U1 BSM0 I2C communication failure
    U2 BSM0 deep discharged
    U3 BSM0 end of life (EOL)
    U4 TBD
    U5 TBD
    U6 BSM1 fault
    U7 BSM1 I2C communication failure
    U8 BSM1 deep discharged
    U9 BSM1 end of life (EOL)
    UA TBD
    UC TBD
    UE BSM2 fault
    UF BSM2 I2C communication failure
    UG BSM2 deep discharged
    UH BSM2 end of life (EOL)
    UI BSM set serial numbers do not match
    UJ TBD
    UK Last charge date greater than eight months
    UM Battery service module ages differ by 2 years or more. See MAP2241 Rack battery module set born-on date mismatch.