MAP2610 SRC BE19390x for rack battery module error
The FRU(s) that are listed in the serviceable event FRU list
after this isolation MAP have a condition that does not require replacement
of the FRU. However, the FRU must be logically reset. Use this MAP
to perform a pseudo repair of the FRU.
MAP2610 Section-1
Procedure
- Are you here because a rack installation failed?
- Yes, at the rear of the rack confirm that the battery enclosure
circuit breakers CB0 and CB1 are set to ON (up) for all battery enclosures.
Then exit this MAP and follow the procedures to restart the rack installation.
- No, continue at the next step.
- Understand this special case repair action:
- The serviceable event FRU
list that contained MAP2610 is followed by one or more rack battery
module FRUs.
- The listed FRUs do not need to be replaced, but they must be logically
reset.
- A FRU will be logically reset when you perform a pseudo
FRU replace. During a pseudo FRU replace, use the standard FRU replacement
procedure, but do not disconnect the cables or physically remove the
FRU.
- Before performing the pseudo repair, confirm
that the battery enclosure circuit breakers CB0 and CB1 are set to
ON (up) for all battery enclosures.
- Return to the HMC repair screen that sent you
here and then select the next FRU to be repaired. Do a pseudo FRU
repair. When the service Information Center (IC) parts replacement
procedure is launched, do not disconnect the cables or physically
remove the FRU. Scroll to the bottom of the IC procedure and then
return to the repair screen that launched the IC screen. Complete
the repair normally.
-
After all serviceable events with SRC BE19390x have been successfully repaired, run
CDA preverify again to verify that all rack battery backup (BBU) problems are now
resolved.
- If running CDA preverify causes more BE19390x serviceable events to
be opened, contact your next level of support.