MAP21A1 DC-UPS fault isolation during installation
The DC-UPS is displaying an error code during the DC-UPS
power checks during an installation. The installation is not yet far
enough to use normal error analysis and repair procedures to repair
the condition.
MAP21A1 Section-1
Procedure
- The DC-UPS does not need to be repaired now; it is repaired
later during the installation.
- Ensure the DC-UPS cables are properly plugged and seated.
- The probable failing FRU can be identified from the DC-UPS
error code and ordered now instead of waiting until the actual repair
is needed later during the installation.
Find the DC-UPS
error code in
MAP2341 Codes on the DC-UPS DSU status display.
| If the error description is for: |
Order: |
| A fan |
The DC-UPS fan assembly |
| Battery service module |
A battery service module set |
| Neither a battery service module or fan |
The DC-UPS DC supply unit (DSU) |
- Continue the installation.