Checking customer voltage with customer CB on (wired)
Procedure
- Remove the lockout tag and/or device that was applied to each customer mainline AC voltage circuit breaker.
- Switch on the customer circuit breaker.
-
Select the condition that applies:
- Customer power is three-phase high voltage (380 - 415 V). Go to the next step.
- Customer power is single-phase (200 - 240 V). Go to step 8.
-
Prepare the multimeter to read line voltage ac.
DANGERDangerous voltages may be present. Do not touch the internal parts (pins and connectors) of the mainline power cable connector.
-
For three-phase high voltage (380 - 415 V), at the mainline power cable connector (DC-UPS end),
measure the customer three-phase voltage to ensure it is within the DC-UPS minimum and maximum input
voltages.
- The nominal customer voltage of three-phase high voltage is 380 - 415 V (phase-to-phase).
- The measured voltage must be between the minimum and maximum voltages of 342 - 456 V.
- Measure the voltages between each pair of voltage pins ( A to B , B to C , and C to A ) on the main line power cable outlet. See Figure 1.
Are all three measured voltages between 342 - 456 V?
- Yes, go to the next step.
- No, inform the customer that the voltages are not correct. Do not continue until the voltages are correct.
Figure 1. Three-phase high voltage (380 - 415 V) mainline power connector at DC-UPS end 
-
At the mainline power cable connector (DC-UPS end), measure the voltage between each voltage
pin and ground ( A to (G), B to (G), and
C to (G)). See Figure 1.
Are the voltages within 10% of each other?
- Yes, go to the next step.
- No, inform the customer that the voltages are not correct. Do not continue until the voltages are correct.
-
At the mainline power cable connector (DC-UPS end), measure the voltage between each voltage
pin and the Neutral pin ( A and Neutral, B
and Neutral, C and Neutral). See Figure 1.
Is the measured voltage 180 - 264 V?
- Yes, go to step 10.
- No, inform the customer that the neutral line measured incorrectly. Do not continue until the customer corrects the situation.
-
Prepare the multimeter to read line voltage ac.
DANGERDangerous voltages may be present. Do not touch the internal parts (pins and connectors) of the mainline power cable connector.
-
For single phase (200 - 240 V), measure the voltage between voltage pins
A and B . See Figure 2.
- The nominal customer voltage of single-phase is 200 - 240 V (phase-to-phase).
- The measured voltage must be between the minimum and maximum voltages of 180 - 264 V.
Is the measured voltage between 180 - 264V?
- Yes, continue with the next step.
- No, inform the customer that the voltages are not correct. Do not continue until the voltages are correct.
Figure 2. Single-phase mainline power connector at DC-UPS end 
- Continue with Connecting the mainline power cables (wired).